Permit: T07CM04306

Parcel: 141354020


Addresses:

10790 E DEEP SKY DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM04306

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/25/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLOSET SHEAR MOVED TO BEDROOM FRONT WALL, NEEDS TO BE NAILED PER <4> ON ENGINEER MOVE OF PANEL
04/24/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
- ANCHOR BOLTS SPACING MAX 24" ON DOUBLE SHEAR WALL MAIN FLOOR BATH
- TIGHTEN DOWN TITEN AT STAIRWALL SHEAR
- DOUBLE FOUNDATION ANCHORING NEEDED ON GARAGE/LIVING ROOM WALL
04/02/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) INSTALL ANCHOR BOLTS
2) STRAP INTERIOR FLOOR BEAMS
03/31/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection 1) INSTALL ALL F STRAPS 1ST & 2ND FLOOR
2) 2ND FLOOR GIRDER LOAD PTS. TO CONTINUE DOWN TO CONCRETE
3) NEED WIND BRACE WEST SIDE 2ND FLOOR
4) FILL ALL HOLE IN HANGERS WITH CORRECT NAILS
5) CMST STRAPS AT TWO SIDES OF GARAGE FRONT
6) FINISH NAILING FLOOR
7) FINISH MID SPAN BLOCKS REAR SHEAR
8) FINISH REVISION FOR SHEAR TRANSFER ABOVE GARAGE
9) FILL GAP AT FLOOR GLU LAM FLOOR TRUSS BEARING GAP
10) STILL FRAMING