Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04302
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/07/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SECONDARY CONDENSATE DRAIN CANNOT TERMINATE INTO THE PRIMARY DRAIN. - SECONDARY MUST TERMINATE TO A CONSPICUOUS LOCATION OR PROVIDE AN OVERFLOW SENSOR. - PROVIDE A TRAP ON SECONDARY DRAIN. - VENT ON TRAPS MUST BE DOWNSTREAM OF THE TRAP - PROVIDE A DISCONNECT SWITCH FOR FAN COIL AS PER PLANS - SECURE LINE SET IN EQUIPMENT ROOM |
|
04/28/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |