Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04302
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL PER APPEAL |
|
05/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WORKING CLEARANCES WERE NOT MAINTAINED 2. PANEL SCHEDULE TO BE AS PER 408.4 -- NO ABBREVIATIONS |
|
05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SPLICES IN UNDERGROUND PULL BOXES TO BE LISTED FOR WET LOCATION. INSTALL BOLTS FOR COVERS 2. OVERCURRENT PROTECTION FOR AIR HANDLER TO BE 15a #12, #14 CIRCUITS 3. CONNECT EQUIPMENT GROUND TO POLES INSTALL LUG TO POLE 4. HAND DRYER TO BE INSTALLED TO GET COMPLETE FINAL |