Inspection History Details
Inspection Status: Cancelled
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2008 | PLUMBING - INTERMEDIATE | Cancelled | PER SAM | |
| 08/01/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WATER PIPE SIZING NOT PER PLAN NO REDLINES ON SITE 2ND LEVEL WC NOT SHOWN ON PLAN WATER TEST DOWN ON SOUTH HALF DWV PEX TOUCHING METAL SLOPE ON LAV DRAIN |
|
| 07/25/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE APPROVED PLANS 2. CHECK WATER PIPING SIZE 3. SECURE PEX AT RISER AND IN WALLS 4. CORRECT EXTERIOR SERVICE AND PROTECT FROM STUCCO 5. CLOSET FLANGES WILL BE INSPECTED AFTER FINISHED FLOOR PRIOR TO SETTING CLOSETS. 6. INSTALL PER UPC INSTALLATION STANDARDS AND CODE SECTIONS - 316.3.1, 316.3.2, 704.4.3, 704.4.5 |
|
| 06/16/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |