Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04291
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/20/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE R-4.2 INSULATION PER 403.2 I.E.C.C (I.E.C.C REQUIRES R-6 C.O.T AMENDED THIS CODE TO ALLOW 4.2) |
|
01/16/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE NON-COMBUSTIBLE MATERIAL BEHIND HOODS AND BEYONE 18" SIDES ALSO 2. PROVIDE SEISMIC RESTRAINTS ON ALL GRILLS |
|
01/13/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/12/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIR ALL TEARS IN INSULATION VAPOR BARRIER 2. COMPLETE DUCT WRAP THROUGH WALL AT RESTROOM 3. COMPLETE INSTALLATION OF CEILING DIFFUSERS 4. COMPLETE INSULATION OF DUCT WORK 5. SEAL ALL DUCT JOINTS 6. RE-DUCT DISHWASHER EXHAUST DUCT |