Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2009 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/08/2009 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER OVERHEAD AT KITCHEN |
|
| 12/18/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER OVERHEAD AT ALL RESTROOMS |
|
| 12/17/2008 | PLUMBING - ABOVE CEILING | Not ready for Inspection | 1. ALL VENTS SHALL BE INSTALLED LEVEL OR GRADED BACK TO FIXTURE BEING SERVED. 2. N/H CAST IRON TO BE SUPPORTED WITHIN 18" OF EACH SIDE AT COUPLING, AND CHANGE OF DIRECTION. WALL IS NOT CONSIDERED SUPPORT. 3. WATER PIPING INSULATION TO BE CONTINUOUS AND USE HARD SECTIONS AND SHIELDS WHERE REQUIRED. 4. CONTRACTOR TO BE VERY CAREFUL NOT TO CONCEAL ANY PLUMBING BEFORE APPROVAL. |
|
| 12/16/2008 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PIPING NOT INSULATED AROUND ELBOWS |