60 W WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04291

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/20/2009 ELECTRIC - FINAL Partial Approval LAST ITEM IS WATER CONDITIONING UNIT
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE VERIFY LISTING & LABELING FOR WATER CONDITIONING EQUIPMENT
2. USE APPROVED EXTENDER RINGS - METAL NOT APPROVED
3. GROUND UNDER COUNTER FIXTURE BASES
4. BOXES MORE THAN 1/4" - 314.20
5. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
6. BREAKER NUMBERING TO MATCH PANEL SCHEDULES
DIMMER PANELS

ALL PREVIOUS ITEMS CORRECTED
02/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COOK ISLAND:
1) IDENTIFY EQUIPMENT GROUND CONDUCTOR
SERVICE LINE:
1) PROTECT CONDUCTORS AT FITTING
2) VERIFY LISTING OF COKE DISPENSER ASSEMBLY
02/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BORDER NEON:
1. USE APPROVED TERMINATION PLATES
2. TIGHTEN LOOSE FITTINGS
3. MAINTAIN NEON TUBING SPACING 1/4" -- 600.41
4. SECURE FLEX CONDUIT WITH GTO CABLING
5. MAINTAIN GTO CLEARANCES 600.32

ROOF: FINISH ANTENNA WORK

OK ROOF EXCEPT AS NOTED
02/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PANEL DIRECTORIES TO BE AS PER 408.4
2. FINISH KITCHEN GFI's
3. PLEASE VERIFY LISTING FOR LV LIGHTS AND TRANSFORMER TO BE ACCESSIBLE
4. MAKE UP NEW TRANSFORMER AS PER ARTICLE 600

ROOF:
1. TIGHTEN LOOSE FITTINGS
2. MAINTAIN WORKING CLEARANCES 110.26
3. MAKE UP NEON TRANSFORMERS PER ARTICLE 600
4. GTO CABLE TO BE IN RACEWAY TO TERMINATION PLATES
02/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
KITCHEN:
1. BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
2. USE APPROVED HARDWARE WITH DEVICES
3. KITCHEN RECEPTACLES TO BE GFI PROTECTED 210.8
4. FINISH SEALS ABOVE WALK-INS - 300.7
5. COLOR CODING FOR CONDUCTORS IN TUCSON AMENDMENTS ARE BLACK, RED, BLUE, 120/240V
BROWN, ORANGE, YELLOW 277/480V
01/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*