Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T07CM04291
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2009 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
02/12/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
02/11/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK OUTSIDE BORDER NEON OK BAKERY, BAR, DINING 1 & 2, FRONT DESK 1. FINISH INSIDE NEON AS DISCUSSED |
|
02/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* BAR: 1. PLEASE VERIFY LISTING & LABELING FOR COKE DISPENSER ASSEMBLY FRONT DESK: 1. PROVIDE SPACERS FOR VENTILATION OF LED TRANSFORMERS PATIO: 1. USE CORRECT GROUNDED CONDUCTOR COLORS PER LABELING IN 200.6 & 210.5 (C) |
|
12/08/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
12/05/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK COOK LINE WALL SOUTH 1. NO MORE THAN 360 DEG. IN CONDUIT RUNS - OUTSIDE 2. TIGHTEN LOOSE FITTINGS |
|