Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/27/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK DINING AREA #2 & FOYER 1. LEAVE OPEN TO CHECK NEON CONNECTIONS |
|
| 01/23/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* TO AVOID REINSPECTION FEES, DO NOT CALL FOR INSPECTION UNTIL PROGRESS ON JOB! |
|
| 01/22/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK SEALOFF's ABOVE WALK-IN FREEZER |
|
| 01/21/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PENDANT LIGHTS DINING #1 OK CANS BAR LOUNGE |
|
| 01/20/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* HOOD: 1. GROUND JUNCTION BOXES 2. BROKEN SHEATHING WALK IN BOXES - SEAL PER 300.7 PENDANT LIGHTS - BOXES OVERFILL 314.16 OK CHEFS LINE OK KITCHEN EXCEPT AS NOTED OK DINING #1 EXCEPT AS NOTED |
|
| 01/13/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* KITCHEN 1. SUPPORT CONDUITS & MC CABLES AS PER CODES 2. SUPPORT FIRE ALARM & VDV CABLING 725.24, 760.24, 300.61, 800.24 |
|
| 12/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CAN PATIO & CONDUITS OK CANS MAIN COOKING OK CANS BATHROOM HALL |
|
| 12/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK NEW LEADS OK BATHROOM CANS |
|
| 12/15/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. GTO CABLE FOR NEON SIGNS NOT ALLOWED OVER 20' FROM TRANSFORMER TO FIRST CONNECTIONS 2. JUNCTION BOXES TO BE ACCESSIBLE MANAGER'S OFFICE OK EMPLOYEE BATHROOMS, MANAGER'S OFFICE PARTIAL CANS BAR, LOUNGE, BAKERY, HOSTESS, DINING #2, ENTRY AND COOKLINE EXCEPT AS NOTED |