Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/15/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LOCKNUT WITH CHASE NIPPLE @ LB CONNECTION TO PANEL FOR GOOD METAL TO METAL CONTACT 2. CIRCUITS ON SPLIT BREAKERS ARE ALL THE SAME PHASE AND REQUIRE SEPARATE NEUTRALS 3. NEED LISTED HUBS FOR TOP ENTRY SEE INSTRUCTIONS ON PANEL DOOR 4. PANEL DIRECTORY NOT PER PLANS 5. SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP COMMERCIAL SERVICE 6. OUTDOOR LIGHTING NOT PER PLAN 7. PLAN CALLS FOR 40 SPACE PANEL BOARD |