Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04253
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* T AND B REPORT OK SMOKE CONTAINMENT REPORT OK HOOD SENSORS (INTERLOCK) TEST OK ACCESS TO BLOWER HOUSING IS IN CONFLICT WITH CURTAIN WALL, BUILDING INSPECTOR WILL APPROVE CORRECTION PRIOR TO BUILDING FINAL. SEE BUILDING INSPECTOR FOR TEMP C OF O |
|
10/01/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTOR TEST OK PROVIDE AIR BALANCE AND SMOKE CONTAINMENT REPORTS PROVIDE INTERLOCK SYSTEM ON HOOD |
|