Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2008 | MECHANICAL - HOODS | Approved | ||
| 09/16/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* SECOND LAYER ON BOTH HOODS OK STILL NEED ACCESS DOORS ON BOTH DUCTS |
|
| 09/12/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1. SECOND LAYER OF FIRE WRAP NOT PROPERLY OVERLAPPED ON LT. SIDE 2. 1ST LAYER OF WRAP ON RT SIDE OK 3. NO ACCESS DOORS INSTALLED AT THIS TIME |
|
| 09/09/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1. WELD LEAK TEST ON RT HOOD GREASE DUCT OK 2. FIRST LAYER OF FIRE WRAP ON LT. HOOD GREASE DUCT OK 3. ACCESS DOORS ON GREASE DUCT ARE MIN. 12" X 12" IF DUCT SIZE ALLOWS |
|
| 09/08/2008 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE AND SEAL ALL MUA DUCT AT HOODS MECHANICAL CONTRACTOR TO BE ON SITE |
|
| 09/05/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* |