Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. INSTALL DUCT SMOKE DETECTORS IN APPROVED LOCATION, PROVIDE SAMPLE TUBE SUPPORT PER INSTALLATION INSTRUCTIONS 2. OK FOR TILES MECHANICAL ONLY |
|
| 09/05/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE DAMPER ACCESS PRIOR TO FINAL OK TO ROCK HARD LIDS MECHANICAL ONLY 2. PROVIDE GREASE DUCT ACCESS DOORS PRIOR TO FINAL 3. LEFT SIDE GREASE DUCT LEAK TEST OK 4. PROVIDE PROPER AMOUNTS OF SCREWS IN STRAPS |