Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2008 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 07/30/2008 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. CLEANOUTS ARE TO BE INSTALLED TURNED AWAY FROM THE BW VALVE 2. SEWER DOWNSTREAM OF THE INTERCEPTOR TO HAVE FULL SIZE VENT |
|
| 06/12/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. PROVIDE FULL SIZE CLEANOUT ON 4" PER PLAN 2. PER RED LINES PROVIDE APPROVED PLAN FOR CHANGES |
|
| 06/04/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. PROVIDE VENT FOR SEWER 2. PROVIDE ALL FLOOR SINK ON APPROVED PLANS FOR RETEST 3. SOUTH SIDE OF GREASE TRAP UNDERGROUND PIPING OK 4. RESTROOM UNDERGROUND PIPING OK |