Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE A MEANS TO CONTROL HOT WATER TEMPERATURE AT PUBLIC USE LAVS BESIDES WATER HEATER NOT TO EXCEED 110 DEG. 2. PROVIDE APPROVED TAILPIECE AT SINK DRAIN. |