Permit: T07CM04244

Parcel: 136347140

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/20/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
15 PSI TEST IS OK
LEFT GAS CARD
11/14/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
100,000 BTU FURNACE 60' FROM METER 1/2" GAS PIPE
NOT ADEQUATE. PROVIDE 3/4" PIPE TO THE FURNACE
ALL OTHER CORRECTIONS OK
11/08/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*