Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04238
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED ROOF ACCESS 2. NEED A LETTER DELETING FLUORESCENT LIGHT |
|
01/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH SCAN ROOM AND EQUIPMENT 2. FINISH ROOF OK OFFICES |
|
01/28/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" -- 314.20 2. EXIT & EM FLOODS TO BE AS PER -- 700.12 3. GROUND SWITCHES AROUND PLASTIC ARC SHIELDS 4. PLEASE VERIFY LISTING OF HUMIDIFIER 5. FINISH VDV CABLING ROOF: 1. SUPPORT CONDUIT - STRANDS, FEEDER, T-STAT 2. TIGHTEN LOOSE FITTINGS 3. FILL UNUSED OPENINGS |
|
01/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BRING GROUNDED CONDUCTOR TO SERVICE DISCONNECT -- 250.24 2. LB TO BE CAPABLE TO BE LOCKED 3. PREVENT OBJECTIONABLE CURRENT |