Permit: T07CM04233

Parcel: 108203250


Addresses:

4172 N FORTUNE LP

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/25/2008 EXT METAL CLIPS/EXT SHEATHING Approved 1) PER CHANGES MADE BY ARCHITECT AND APPROVAL BY LEE RAY
03/20/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
CANCELED PER LARRY
03/13/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) INSPECTED ALL EXT. SHEATHING AND HARDWARE-EVERYTHING OK
2) WAITING ON REVISED ENGINEERING FOR CHANGES
3) PROCEED AT YOUR OWN DISCRETION ON STUCCO MESH
03/10/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER LARRY
02/29/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER LARRY
02/25/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL ENGINEERED CHANGES NEED TO HAVE CITY APPROVED, FAILURE TO DO SO NEXT TIME WILL RESULT IN A REFEE
02/22/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO TAKE DRAWINGS WITH ENGINEERED CHANGES TO PLAN CHECKING FOR APPROVAL
2) NOTE: ENGINEERED APPROVING CHANGES NOT THE SAME ENGINEER AS STAMPED ON APPROVED PLANS
02/20/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) C2 COLUMN NEEDS TO BE MOVED OR ENGINEERED FIX
2) C2 AND C1 NEED SIMPSON AC4 OR HAVE ENGINEERED FIX
3) PLANS CALL FOR SHEAR SHEATHING TO BE HORIZONTAL AND ?
4) ITEM #1 NOT CORRECTED
01/14/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING A34 PER DETAIL 2/SD1
2) C2 POST MISSING CONNECTION-SIMPSON AC4
3) DRAWINGS SHOW C1 (COLUMNS) AND BEAM PER 5/SD1-NOT BUILT PER PLANS. REVISE OR COMPLY
01/04/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAILING ON SHEARWALLS AT GARAGE NOT PER PLAN
2) TJI NEEDS WEB STIFFNERS PER 1/SD1
3) NEED DBL STUDS ON CORNER OF ALL SHEARWALL HOLDOWNS
4) MISSING 2 X 6 BLOCKING ON LEDGER AT GARAGE
5) STOPPED INSPECTION AT GARAGE