Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07CM04228
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2008 | FIRE SPKLR - FINAL | Approved | ||
07/03/2008 | FIRE SPKLR - FINAL | Not ready for Inspection | 2 heads too close together 1 painted head 1 upright missing need 1/2" orifice in inspectors test |