Permit: T07CM04228

Parcel: 13623007Z

Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Permit Number - T07CM04228

Inspection Description - MECHANICAL - HOOD SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2008 MECHANICAL - HOOD SYSTEMS Approved IVRS - Inspection :*
07/01/2008 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
CHECKED 2ND LAYER OF FIRE WRAP
INSTALL ACCESS DOOR
PROVIDE MIN. 1" DRAIN LINE ON 12.5 TON UNIT
INSTALL FRESH AIR INTAKES
NEED TO TEST DUCT SMOKE DETECTORS
06/30/2008 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
06/27/2008 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1ST LAYER OF GREASE DUCT WRAP OK
SPACING BETWEEN TRUSSES MAKES SECOND LAYER
QUESTIONABLE
06/25/2008 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
06/24/2008 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
OK FOR FIRST LAYER OF WRAP
06/23/2008 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
05/20/2008 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
PROVIDE A METAL STUD WALL AT HOOD AS PER PAGE H2 OF PLANS & 2006 IMC

2006 IMC ALSO REQUIRES 2 LAYERS OF FIRE WRAP AND A HEAT SENSOR IN THE DUCT