Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2008 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection :* | |
| 07/01/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* CHECKED 2ND LAYER OF FIRE WRAP INSTALL ACCESS DOOR PROVIDE MIN. 1" DRAIN LINE ON 12.5 TON UNIT INSTALL FRESH AIR INTAKES NEED TO TEST DUCT SMOKE DETECTORS |
|
| 06/30/2008 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* | |
| 06/27/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1ST LAYER OF GREASE DUCT WRAP OK SPACING BETWEEN TRUSSES MAKES SECOND LAYER QUESTIONABLE |
|
| 06/25/2008 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* | |
| 06/24/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* OK FOR FIRST LAYER OF WRAP |
|
| 06/23/2008 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* | |
| 05/20/2008 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* PROVIDE A METAL STUD WALL AT HOOD AS PER PAGE H2 OF PLANS & 2006 IMC 2006 IMC ALSO REQUIRES 2 LAYERS OF FIRE WRAP AND A HEAT SENSOR IN THE DUCT |