Permit: T07CM04228

Parcel: 13623007Z

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM04228

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2008 PLUMBING - FINAL Approved
07/10/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
NEED AS BUILT APPROVAL
07/08/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
NEED CITY APPROVED REVISION FOR ADDITIONAL HAND SINK
07/07/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. APPROVED PLANS NOT ON SITE
2. ALSO, YOUR IRRIGATION ASSEMBLY IS TOO LOW AND IS MISSING THE UNION
3. THE HANDLE UPSTREAM OF DOMESTIC RP IS BURIED
4. MIXING OF DISSIMILAR METALS IS PROHIBITED IN NEW CONSTRUCTION IS GALVANIZED ALLOWED PER PLAN SPECIFICATIONS?
07/01/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
AFTER HRS. CK #0608127759 - $150.00

RECEIVED BACTERIA REPORT FOR POTABLE WATER
RECEIVED (7) IN HOUSE BACKFLOW CERTIFICATIONS

1. NEED COMPLETION & INSPECTION OF WATER HEATER VENT BY MECH. INSPECTOR BEFORE GAS IS ENERGIZED
2. NEED CITY APPROVED STAMPED REVISION FOR ADDITION OF HAND SINK PER PIMA COUNTY HEALTH

GAS CARD TO GENERAL CONTRACTOR

1-480-214-3626
06/30/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE SEPARATE SOURCE OF WATER FOR CHEMICAL ADDITION AT 3-COMP SINK & JANITOR SINK
2. PROVIDE IN HOUSE BACKFLOW CERTIFICATIONS
3. PROVIDE SEPARATE FULL SIZE DRAINS FOR ICE MACHINE
4. SEPARATE T&P DRAIN FROM RP DRAIN
5. COMPLETE INSULATION AT WATER HEATER
6. COMPLETE VENTING FOR WATER HEATER
7. BACTERIA REPORT TO HAVE ADDRESS OF THIS JOB
8. PROVIDE CORRECT CRITICAL LEVEL AT URINAL
9. FLOOR DRAINS TO BE FLUSH TO FLOOR