Permit: T07CM04228

Parcel: 13623007Z

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04228

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OUTDOOR EM LIGHTING NOT WORKING. TO BE CIRCUITED PER PLAN. NEED CONSTANT FEED TO LIGHT FIXTURES
2. STILL NEED WEATHERPROOF BOX @ DISCONNECT FOR
ICE MAKER
3. BLOWER FAN ABOVE BACK DOOR TO HAVE DISCONNECTING MEANS.
07/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE ITEM #5 FOR INSPECTION ON 7/2/08
2. OUTDOOR EM LIGHTING NOT WORKING
3. INSTALL 15 AMP FUSES IN DISCONNECT FOR EVAP COOLER
4. INSTALL WEATHERPROOF BOX FOR DISCONNECT FOR ICE MAKER CONDENSING UNIT.
07/02/2008 ELECTRIC - FINAL Denied 1. NEED PANEL DIRECTORIES
2. NEED BOX EXTENSION ON RECEPT IN WOOD PANELS
3. LIGHT FIXTURES CEILING DINING RM TO HAVE TIE WIRES
4. RECEPT MISWIRED UNDER DRINK FOUNTAIN
5. ALL 15 & 20 AMP 125V RECEPTACLES IN KITCHEN TO BE GFI PROTECTED
6. SWITCH FOR FREEZER FAN COIL NOT WORKING
7. FINISH WORK ON ANSUL SYSTEM
8. EM LIGHTING NOT WORKING CHECK ALL
9. PROPERLY GROUND A/C DISCONNECTS
10. INSTALL PROTECTIVE BUSHINGS ON #4 CONDUCTORS
11. PROPERLY INSTALL CHASE NIPPLES
12. ALL ROOFTOP RECEPTS TO BE GFI
13. PROPERLY GROUND LIGHT POLES