Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04228
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/09/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OUTDOOR EM LIGHTING NOT WORKING. TO BE CIRCUITED PER PLAN. NEED CONSTANT FEED TO LIGHT FIXTURES 2. STILL NEED WEATHERPROOF BOX @ DISCONNECT FOR ICE MAKER 3. BLOWER FAN ABOVE BACK DOOR TO HAVE DISCONNECTING MEANS. |
|
07/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEM #5 FOR INSPECTION ON 7/2/08 2. OUTDOOR EM LIGHTING NOT WORKING 3. INSTALL 15 AMP FUSES IN DISCONNECT FOR EVAP COOLER 4. INSTALL WEATHERPROOF BOX FOR DISCONNECT FOR ICE MAKER CONDENSING UNIT. |
|
07/02/2008 | ELECTRIC - FINAL | Denied | 1. NEED PANEL DIRECTORIES 2. NEED BOX EXTENSION ON RECEPT IN WOOD PANELS 3. LIGHT FIXTURES CEILING DINING RM TO HAVE TIE WIRES 4. RECEPT MISWIRED UNDER DRINK FOUNTAIN 5. ALL 15 & 20 AMP 125V RECEPTACLES IN KITCHEN TO BE GFI PROTECTED 6. SWITCH FOR FREEZER FAN COIL NOT WORKING 7. FINISH WORK ON ANSUL SYSTEM 8. EM LIGHTING NOT WORKING CHECK ALL 9. PROPERLY GROUND A/C DISCONNECTS 10. INSTALL PROTECTIVE BUSHINGS ON #4 CONDUCTORS 11. PROPERLY INSTALL CHASE NIPPLES 12. ALL ROOFTOP RECEPTS TO BE GFI 13. PROPERLY GROUND LIGHT POLES |