Permit: T07CM04228

Parcel: 13623007Z

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T07CM04228

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
07/07/2008 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
06/27/2008 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
TO ARRANGE FOR AFTER HRS. INSPECTION
CALL RAY MAJUTA @ 909-4891
06/26/2008 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1. GROUND ROD CUT. HAVE 2 NEW GROUND RODS ON SITE FOR SERVICE INSPECTION. NEED TO BE DRIVEN WHILE INSPECTOR IS ON SITE. NEED TO HAVE CHECK FOR $150 TO PAY FOR THIS AFTER HRS. INSPECTION TO GET ANY FURTHER INSPECTIONS DONE. WORK FOR SERVICE NOT COMPLETE.
HAVE 100% COMPLETE TO AVOID REFEE.
06/25/2008 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1. BOND SERVICE RISERS NEC 250.92
2. INSTALL PROTECTIVE BUSHING FOR
CONDUCTORS #4 & LARGER - NEC 300
3. BRACE CABLES IN CT CABINET PER INSTRUCTIONS ON DOOR
4. BOND RACEWAY BETWEEN CT CABINET AND DISCONNECT
NEC 250.92
5. INSTALL NEUTRAL KIT SERVICE DISCONNECT
6. NEED APPROVED REVISED PLAN FOR CHANGES TO SERVE
7. WORK NOT COMPLETE RECALL WHEN READY