Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T07CM04228
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2008 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
06/27/2008 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* TO ARRANGE FOR AFTER HRS. INSPECTION CALL RAY MAJUTA @ 909-4891 |
|
06/26/2008 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* 1. GROUND ROD CUT. HAVE 2 NEW GROUND RODS ON SITE FOR SERVICE INSPECTION. NEED TO BE DRIVEN WHILE INSPECTOR IS ON SITE. NEED TO HAVE CHECK FOR $150 TO PAY FOR THIS AFTER HRS. INSPECTION TO GET ANY FURTHER INSPECTIONS DONE. WORK FOR SERVICE NOT COMPLETE. HAVE 100% COMPLETE TO AVOID REFEE. |
|
06/25/2008 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* 1. BOND SERVICE RISERS NEC 250.92 2. INSTALL PROTECTIVE BUSHING FOR CONDUCTORS #4 & LARGER - NEC 300 3. BRACE CABLES IN CT CABINET PER INSTRUCTIONS ON DOOR 4. BOND RACEWAY BETWEEN CT CABINET AND DISCONNECT NEC 250.92 5. INSTALL NEUTRAL KIT SERVICE DISCONNECT 6. NEED APPROVED REVISED PLAN FOR CHANGES TO SERVE 7. WORK NOT COMPLETE RECALL WHEN READY |