Permit: T07CM04228

Parcel: 13623007Z

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/07/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G FOR DRIVE THRU MENU BOARD
2. MARK "SERVICE DISCONNECT"
3. BOND GAS, WATER TO SERVICE. GEC TO TERMINATE ON NEUTRAL BAR
4. RECEIVED CK#20362 FOR AFTER HRS. INSP. ON 6/26/08
5. PARTIAL INSPECTION FOR SERVICE. DO NOT ENERGIZE PANEL N BEFORE ANOTHER INSPECTION. LOCK OUT SERVICE DISCONNECT.
04/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 2 - 4" PVC FROM TEP XFMR TO CT CABINET
2. OK 2 - 3" PVC FROM CT CABINET TO PANEL M
3. OK 2 1/2" TO PANEL B
4. OK 2" TO PANEL A
5. OK 1 1/2" TO PANEL C
6. OK 2" TO PANEL D
7. OK 1 1/4" TO SHUNT TRIP LOCATION FROM PANEL M
8. INSTALL WARNING RIBBON ABOVE SERVICE RACEWAY PER NEC 300.5
9. OK 1" IN SLAB FOR POLE LIGHTS