Permit: T07CM04227

Parcel: 13734001D

Inspection Status: Cancelled

Inspection History: PLUMBING - FINAL

Permit Number - T07CM04227

Inspection Description - PLUMBING - FINAL

Inspection Status - Cancelled

Date Description Inspector Results Comments
09/12/2008 PLUMBING - FINAL Cancelled IVRS - RI canceled
09/12/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE MEANS FOR WATER HAMMERING AT WASHER BOX
2. PROVIDE SUPPORT AND PRIMER & GLUE FOR PVC PIPING
3. COMPLETE INSTALL OF MOP SINK
4. COMPLETE LIST FROM 7/30/08
08/13/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 7/30/08
07/30/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLY W/COT REQUIREMENTS FOR FOOT SPAS;
HANDOUT PROVIDED

1. ANSI LISTING
2. DIRECT CONN FOR GRAVITY DRAINS
ALSO, PVC PRIMER REQUIRED ON PVC JOINTS

PROVIDE ACCESS OF RPA INDIRECT WASTE RECEPTORS
PER 804.1 WHICH DOES NOT ALLOW RECEPTORS IN ANY PORTION OF THE BUILDING NOT IN GENERAL USE; COMMON WALL BETWEEN SUITES.

ALSO, PROVIDE ACCESS PER 603.3 AND INSTALLATION STANDARDS. 4" NEEDED ABV HIGHEST TC
UNIONS REQUIRED AT RPA's AND AT RP
SUPPORT EXP. TANK AND RECIRC. PUMP CORRECT LEAK
PROVIDE BACKFLOW CERTS AND BAC.T REPORT