Permit: T07CM04227

Parcel: 13734001D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04227

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NAIL SPA EQUIPMENT CALL FOR GFCI PROTECTION
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
USE APPROVED EXTENDER RINGS
3. EXIT LIGHTS TO BE ON CIRCUITS FOR AREA SERVED 700.12
4. TIGHTEN LOOSE WATER HEATER FITTING
5. WHERE IS INTERLOCK CONTACTORS AS PER PLANS?

ROOF:
1. TIGHTEN LOOSE FITTINGS
2. SECURE SUPPORT STAND TO STRUCTURE
3. LABEL DISCONNECT
4. PROTECT CARFLEX FROM SHARP METAL EDGES