Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04227
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NAIL SPA EQUIPMENT CALL FOR GFCI PROTECTION 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 USE APPROVED EXTENDER RINGS 3. EXIT LIGHTS TO BE ON CIRCUITS FOR AREA SERVED 700.12 4. TIGHTEN LOOSE WATER HEATER FITTING 5. WHERE IS INTERLOCK CONTACTORS AS PER PLANS? ROOF: 1. TIGHTEN LOOSE FITTINGS 2. SECURE SUPPORT STAND TO STRUCTURE 3. LABEL DISCONNECT 4. PROTECT CARFLEX FROM SHARP METAL EDGES |