Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/05/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AIR BALANCE REPORT OK WITH THE FOLLOWING EXCEPTION EF-3 IS THE WRONG FAN PROVIDE FAN CALLED OUT ON SCHEDULE, THIS FAN IS OVER PULLING MAKE AIR BY 680CFM DUCT DETECTOR TEST OK 9 UNITS TOTAL |
|
| 07/24/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT FOR HVAC AND KITCHEN EXHAUST AND MAKE UP AIR SYSTEMS, ALSO, PROVIDE DUCT SMOKE DETECTOR TESTING REPORT OR HAVE HVAC CONTRACTOR ON SITE TO PERFORM TEST |