Permit: T07CM04221

Parcel: 13734001D


Addresses:

1690 W VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04221

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2008 MECHANICAL - ABOVE CEILING Approved
07/10/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
SCREW FLUE PIPE TO HEATER
BRING COMBUSTION AIR 1 FOOT OFF FLOOR
07/03/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
COMBUSTION AIR DUCTS MUST BE SEPARATE
CLEANOUT NOT ACCESSIBLE
INSULATION ON ACCESS DOOR DOES NOT APPEAR TO BE INSTALLED CORRECTLY. PROVIDE INSTALL INSTRUCTIONS FOR ACCESS DOOR.
06/26/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE ACCESS TO CLEANOUT ON GREASE DUCT,
MOVE M.U.A TO ACCURATE
2. OK FOR TILES IN DINING ROOM MECHANICAL ONLY
06/03/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RETURN DUCTS NOT CONNECTED
2. NO SAFETY WIRES ON REGISTERS & GRILLS
3. DUCT INSULATION NOT COMPLETE
4. EXHAUST IN RESTROOMS NOT COMPLETE
5. SUPPLY DUCT NOT COMPLETE
6. MUA DUCT NOT COMPLETE
7. SINGLE WALL FLUE PIPE NOT ALLOWED ABOVE CEILING
8. EXHAUST FAN DUCT TO TERMINATE PER DETAIL MD0017
9. PROVIDE OBD's PER PLANS
10. PROVIDE COMBUSTION AIR AT WATER HEATER PER PLANS
11. REGISTERS AND GRILLS NOT AS SPEC'D ON PLANS