Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04221
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2008 | MECHANICAL - ABOVE CEILING | Approved | ||
07/10/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* SCREW FLUE PIPE TO HEATER BRING COMBUSTION AIR 1 FOOT OFF FLOOR |
|
07/03/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* COMBUSTION AIR DUCTS MUST BE SEPARATE CLEANOUT NOT ACCESSIBLE INSULATION ON ACCESS DOOR DOES NOT APPEAR TO BE INSTALLED CORRECTLY. PROVIDE INSTALL INSTRUCTIONS FOR ACCESS DOOR. |
|
06/26/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE ACCESS TO CLEANOUT ON GREASE DUCT, MOVE M.U.A TO ACCURATE 2. OK FOR TILES IN DINING ROOM MECHANICAL ONLY |
|
06/03/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RETURN DUCTS NOT CONNECTED 2. NO SAFETY WIRES ON REGISTERS & GRILLS 3. DUCT INSULATION NOT COMPLETE 4. EXHAUST IN RESTROOMS NOT COMPLETE 5. SUPPLY DUCT NOT COMPLETE 6. MUA DUCT NOT COMPLETE 7. SINGLE WALL FLUE PIPE NOT ALLOWED ABOVE CEILING 8. EXHAUST FAN DUCT TO TERMINATE PER DETAIL MD0017 9. PROVIDE OBD's PER PLANS 10. PROVIDE COMBUSTION AIR AT WATER HEATER PER PLANS 11. REGISTERS AND GRILLS NOT AS SPEC'D ON PLANS |