Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04221
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT MC CABLE FOR EXH. FAN IN BATHROOM 2. OPEN J-BOX IN SOUTH END OF KITCHEN CEILING |
|
07/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK DINING AREA ONLY |
|
06/20/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENING IN BOX 2. SUPPORT CONDUIT AS PER CODE 3' & 10' 3. CORRECTLY SUPPORT MC CABLE - ONLY ONE PER STRAP AND ATTACHED TO WIRES 4. ATTACH SUPPORT BRACKET TO BOX 5. MC CABLE TO BE AS PER 300.11 INDEPENDENT 6. BOXES OVERFILLED 7. SUPPORT VDV CABLING 725.24, 800.24, 300.11 8. FINISH KITCHEN 9. SEAL UNUSED CONDUIT OPENINGS |
|
06/19/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* BLD. LOCKED RECALL INSPECTION |
|
06/03/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEISMIC WIRE REQUIRED FOR ALL GRID LIGHT FIXTURES 2. MC CABLE TO BE SUPPORTED TO WIRES FOR ELECTRICAL SUPPORT ONLY, DO NOT USE CEILING GRID WIRES 3. TRACK LTG. NOT INSTALLED OVER CASHIER AREA 4. MC CABLE LONGER THAN 6' TO BE SUPPORTED WITHIN 12" OF TERM. AND AT 6' INTERVALS PER CODE 5. MC CABLE IN SOFFIT NOT TERMINATED AND SUPPORTED 6. KITCHEN AREA NOT READY |