Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONDUIT & CABLE ROUGH, BE ADVISED THAT SHALLOW P-RINGS THAT ARE BACK MORE THAN 1/4" PER NEC WILL NEED EXTENDER RINGS. |
|