Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MANUFACTURES CLIPS TO BE EFFECTIVE AND SECURELY ATTACHED TO GRID - 410.16 2. BOXES MORE THAN 1/4" AND 1/8" AROUND - 314.20 & 21 3. PANEL CIRCUIT DIRECTORY TO BE AS PER 408.4 NO ABBREVIATIONS 4. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 5. CORD NOT ALLOWED ABOVE CEILING - 400.7 & 8 6. SUPPORT VDV CABLING 725.24 (T-STAT) 7. RECEPTACLE FOR DRINKING FOUNTAINS NOT ACCESSIBLE 8. WHERE ARE BREAKROOM GFCI's 9. 1ST FLOOR ONLY PARTIAL INSPECTION |