Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 07/03/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) PROPERLY BOND SERVICE RISER NEED 2/0 TO ? CHAIN |
|
| 07/02/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO POST BOND FOR TEMP POWER TO TEST 2. INSTALL MAIN BONDING JUMPER. PROVIDE PANEL INSTRUCTIONS. 3. BONDING JUMPER TO SERVICE RISER NOT SIZED PROPERLY 4. BOND GAS, WATER AND SPRINKLER TO SERVICE |