Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T07CM04196
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/13/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST TENSION TAB NEEDED AT WATER HOSE BIB 2) OUTLET NOT ALLOWED UNDER BREAKFAST BAR 3) GFI UPSTAIR BATH DOES NOT RESET 4) DISCONNECT FOR FAN UNIT NOT ACCESSIBLE 5) OUTLET IN LIVING ROOM WEST WALL WITHIN 6' OF KITCHEN SINK NOT GFI PROTECTED 6) DRYER VENT EAST SIDE STCCOED SHUT |