Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/05/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CHERYL |
|
| 03/04/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE SEAL CHASE AT HALLWAY 2) BLOCK DUCT VENTS 3 SIDES 3) FIRE BLOCKING NEEDS MINIMUM 3/4 PLYWOOD OR DBL 1/2 HALLWAY CHASES 4) NEED TO INSULATE ALL BOTTOM PLATES EXT WALLS 5) CEILING BLOCK FOR SHEETROCK AT KITCHEN 6) CUT EXISTING UFER AT KITCHEN 7) NEED TO REPAIR CONCRETE SLAB AT MASTER BATH |
|
| 02/28/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FOLLOW ALL APPROVED PLANS/DETAILS 2) PROVIDE A COMPLETE WATER TEST ON ALL PLUMBING |