Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LIGHT FIXTURES TO BE PERMANENTLY WIRED 2. STRAP PVC CONDUIT 3. USE APPROVED SPLICE CONNECTORS WITH ALL CONDUCTORS 4. USE APPROVED BOXES FOR DEVICES 5. PLANS NOT REFLECTIVE OF ALL ELECTRIC INSTALLED ALSO, NEED LOADS & PANEL SCHEDULES 6. MULTI-POLE TERMINATIONS AT DISCONNECT 7. ILLUMINATION IS NEEDED AT INDOOR ELECTRICAL PANEL & DISCONNECT |