Permit: T07CM04164

Parcel: 12705078A


Addresses:

1080 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LIGHT FIXTURES TO BE PERMANENTLY WIRED
2. STRAP PVC CONDUIT
3. USE APPROVED SPLICE CONNECTORS WITH ALL CONDUCTORS
4. USE APPROVED BOXES FOR DEVICES
5. PLANS NOT REFLECTIVE OF ALL ELECTRIC INSTALLED ALSO, NEED LOADS & PANEL SCHEDULES
6. MULTI-POLE TERMINATIONS AT DISCONNECT
7. ILLUMINATION IS NEEDED AT INDOOR ELECTRICAL PANEL & DISCONNECT