Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/13/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PANEL DIRECTORY NOT IN 2. ON ROOF - BRANCH J-BOX OVERFILLED, WIRE NUTS OVERFILLED, GROUND TO BOX UNDERSIZED, STRAP FLEX WITHIN 12" OF ENCLOSURES 3. CHECK ECI FOR CORRECT INTERLOCK PER PLAN - AC DISCONNECTS RATED FOR 60 AMP? 4. METER BASE & SERVICE DISCONNECT APPEAR NEW NEED TO CHECK PERMIT & INSPECTION |
|
| 02/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL AND HARD LID COVER PROTECT MC @ WINDOW AREAS AS NEEDED |