Permit: T07CM04160

Parcel: 11105046F

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/21/2008 ELECTRIC - INTERMEDIATE Approved
03/13/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PANEL DIRECTORY NOT IN
2. ON ROOF - BRANCH J-BOX OVERFILLED, WIRE NUTS OVERFILLED, GROUND TO BOX UNDERSIZED, STRAP FLEX WITHIN 12" OF ENCLOSURES
3. CHECK ECI FOR CORRECT INTERLOCK PER PLAN - AC DISCONNECTS RATED FOR 60 AMP?
4. METER BASE & SERVICE DISCONNECT APPEAR NEW NEED TO CHECK PERMIT & INSPECTION
02/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL AND HARD LID COVER
PROTECT MC @ WINDOW AREAS AS NEEDED