Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL WIRES BELOW 8' TO BE PROTECTED FROM DAMAGE (SHEETROCK OR CONDUIT) 2) KITCHEN AND BATH RECEPTACLES TO BE GFI 3) GROUND WIRE IN PANEL TO BE CONTINOUS OR CONNECTED WITH NON REVERSIBLE MEANS (CAD WELD) OR APPROVED CRIMP CONNECTORS 4) FINAL WILL BE DONE AFTER ELECTRIC IS RECONNECTED |