Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE R8 DUCT INSULATION ON ALL DUCT IN THE ATTIC. BLOCK & CLAMP PVC EVERY 4' & PAINT ALL WITH LATEX PAINT RESUPPORT EXHAUST DUCT IN ATTIC & PUT BACK ANY DAMAGED INSULATION. PROVIDE A MEANS FOR DRAINING CONDENSOR WATER |
|
| 12/17/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A GFI SERVICE RECEPTACLE ON ROOF - PROVIDE AN ACCESS DOOR FOR BAROMETRIC DAMPER - SEAL ROOF JACKS BETTER - SUPPLY DUCT ON ROOF IS LEAKING AIR - PROVIDE MIN. R8 DUCT IN ATTIC - INSULATE ALL SHEETMETAL FITTINGS WITH R8 INSULATION - PROVIDE SUPPORT ON T-WYES - CONDENSATE DRAIN CANNOT BE REDUCTED AND CANNOT DRAIN ON THE PATIO - PAINT EXPOSED PVC W/LATEX PAINT - BLOCK & CLAMP EVERY 4' |
|
| 12/06/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY APPLE PLUMBING |
|
| 11/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL SERVICE ACCESS PANELS MUST BE ACCESSIBLE 2) FLEX CONNECTORS TO DUCTS ARE NOT REQUIRED 3) IS SLOPE REQUIRED TO CONDENSATE DRAIN BY MANUFACTURES INSTRUCTIONS ? 4) INSTALL WASHERS ON SEAL TITE CONNECTION AT S.W. CORNER OF UNIT WHERE NUT IS COMING THRU HOLE |