Permit: T07CM04129

Parcel: 136321610


Addresses:

4670 S BAYPORT PL

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/18/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE R8 DUCT INSULATION ON ALL DUCT IN THE ATTIC.
BLOCK & CLAMP PVC EVERY 4' & PAINT ALL WITH LATEX PAINT
RESUPPORT EXHAUST DUCT IN ATTIC & PUT BACK ANY DAMAGED INSULATION.
PROVIDE A MEANS FOR DRAINING CONDENSOR WATER
12/17/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
12/10/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A GFI SERVICE RECEPTACLE ON ROOF
- PROVIDE AN ACCESS DOOR FOR BAROMETRIC DAMPER
- SEAL ROOF JACKS BETTER
- SUPPLY DUCT ON ROOF IS LEAKING AIR
- PROVIDE MIN. R8 DUCT IN ATTIC
- INSULATE ALL SHEETMETAL FITTINGS WITH R8 INSULATION
- PROVIDE SUPPORT ON T-WYES
- CONDENSATE DRAIN CANNOT BE REDUCTED AND CANNOT DRAIN ON THE PATIO
- PAINT EXPOSED PVC W/LATEX PAINT
- BLOCK & CLAMP EVERY 4'
12/06/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY APPLE PLUMBING
11/28/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL SERVICE ACCESS PANELS MUST BE ACCESSIBLE
2) FLEX CONNECTORS TO DUCTS ARE NOT REQUIRED
3) IS SLOPE REQUIRED TO CONDENSATE DRAIN BY MANUFACTURES INSTRUCTIONS ?
4) INSTALL WASHERS ON SEAL TITE CONNECTION AT S.W. CORNER OF UNIT WHERE NUT IS COMING THRU HOLE