Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2007 | FIRE SPKLR - FINAL | Approved | ||
| 10/25/2007 | FIRE SPKLR - FINAL | Denied | 1. Correct sprinkler coverage in room by sink. 2. Need up to date fire alarm and fire sprinkler test, last on file shows 10/08/2004. These inspections are to be done once a year. 3. Need up to date fire alarm check valve inspection. This inspection is to be done every 5 years, last on file 10/1998. |