Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL 1. SUPPORT VDV AS PER 815.6 OR 820.6 2. SUPPORT CONDUIT 3. BOX TO BE WITHIN 1/8" OF DRYWALL - 314.21 |
|
| 10/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND @ 6' INTERVALS NOT LAYING ON OTHER EQUIPMENT, RACEWAYS 2. RELOCATED CEILING FIXTURES TO BE SECURED TO GRID 3. GROUND RECEPTACLE J-BOX 4. HAVE OPEN J-BOX IN CEILING 5. NEED K.O PLUGS (2) IN SWITCH BOX |