Permit: T07CM04128

Parcel: 12511196A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/31/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
1. SUPPORT VDV AS PER 815.6 OR 820.6
2. SUPPORT CONDUIT
3. BOX TO BE WITHIN 1/8" OF DRYWALL - 314.21
10/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND @ 6' INTERVALS NOT LAYING ON OTHER EQUIPMENT, RACEWAYS
2. RELOCATED CEILING FIXTURES TO BE SECURED TO GRID
3. GROUND RECEPTACLE J-BOX
4. HAVE OPEN J-BOX IN CEILING
5. NEED K.O PLUGS (2) IN SWITCH BOX