Permit: T07CM04127


Addresses:

8940 E RITA PARK DR

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/16/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1" PVC U.G @ SOUTH DRIVEWAY FOR MONUMENT SIGN
06/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 11 POLE BASES AS INDICATED ON PARSONS PLAN E101
05/12/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK EXTENSION ON PVC RELOCATION FOR PERSONNEL OFFICE POWER PANELS
2. OK 2ND FLOOR SLAB MC HOMERUNS PERSONNEL OFFICE
05/09/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
05/05/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G PVC CONDUITS FROM BUILDING
TO 400 K.W GENERATOR
05/01/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3/0 CONNECTION TO COLUMNS 2, 4, 8 ON P LINE
2. OK 3/0 UFER GROUND TO XFMRS T-NL15A & T-NL15C
04/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 4 - 4" PVC SOUTHSIDE OF BUILDING FOR TELECOMMUNICATION FROM 1 TO 9 LINE.
04/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UFER GROUND CONNECTIONS FROM SLAB TO
FOOTING 1 THRU 12 ON A-LINE
04/24/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G PULL BOX FOR DATA WEST OF PUMP HOUSE
2. OK U.G BRANCH CIRCUITS AND FEEDERS 12 LINE A THRU H
04/23/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3/0 CONNECTION FROM UFER TO COLUMNS @ 8, 10, 11 ON B LINE
2. OK 3/0 CONNECTION TO WATER MAIN FROM UFER
3. OK 3/0 GEC FROM UFER TO XFMR T-NL2
4. OK 3/0 CONNECTION FROM UFER TO COLUMN @ P10
04/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G IN MSB-3 ELECTRIC ROOM
2. OK GROUNDING FOR XFMRS @ MSB-3
04/11/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/10/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK PVC U.G FOR 2 POLE LIGHTS NORTHWEST LOT
2. OK PVC U.G FOR BRANCH CIRCUITS ALONG Q LINE
FROM 1 TO 8
04/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3/0 UFER ALONG 1 LINE FROM Q TO J
2. OK 2 - 2" PVC FROM EH-1 @ Q8 TO EH3 @ A12 ALONG MFL LINE
04/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK REPAIRS TO (4) 3/0 UFERS
2. OK U.G PVC FOR BRANCH CIRCUITS ON Q LINE FROM 1 TO 3
04/07/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/04/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/03/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3/0 UFER PUMP HOUSE
2. OK 3/0 UFER GUARD HOUSE
3. OK U.G PVC FOR POLE LIGHTS NORTHWEST LOT AS INDICATED ON PLAN E-101
4. OK 8 POLE BASES NORTHWEST LOT AS INDICATED
ON PLAN E-101
04/02/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G FOR 4 POLES NORTHWEST LOT AS INDICATED
ON PLAN E-101
04/01/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G PVC FOR 2 POLES
NORTH WEST LOT
03/31/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC U.G FOR BRANCH CIRCUITS FROM 8-12 ON A LINE
03/28/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
03/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 10 POLE BASES EMPLOYEE SOUTH LOT
03/26/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 12 POLE BASES TRUCKERS PARKING LOT
03/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK REPAIRS ON A LINE UFER GROUND (5) REPAIRS
LINES 16 TO 28
2. OK REPAIR TO UFER GROUND ON LINE Q8
03/24/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
U.G AT PUMP HOUSE AS INDICATED ON PLAN E101
PRIMARY TO PUMP HOUSE XFMR #4
03/21/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 - 5" PRIMARY PVC FROM XFMR #1 TO PUMP HOUSE
03/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- REPAIR UFER & CONDUITS AT MSD-3
- OK REMAINDER OF DATA (4) 2" PVC FROM GUARD SHACK, PULL BOX TO BLD.
03/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS DATA & POWER FROM GUARD HOUSE TO INLINE PULL BOX
03/12/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSONS PLAN E-111
03/11/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
03/10/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 1" U.G FOR POLE LIGHTS NORTHEAST TRUCKERS LOT AS INDICATED ON E-101
2. OK U.G AS INDICATED ON PARSONS PLAN E-111
03/07/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 4- 5" PVC PRIMARIES CONTINUED TO SWITCH LOCATION
2. OK 1" U.G FOR POLE LIGHTS NORTHEAST LOT AS INDICATED ON E-101
03/05/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1" U.G FOR POLE LIGHTS NORTHEAST LOT AS INDICATED ON E-101
03/04/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G TURN UPS INTO 6-21 ELECTRIC ROOM
2. OK SECONDARY PVC FROM MSB-1 & MSB-2
TO XFMR #1 & XFMR #2
3. OK 4 - 5" PVC PRIMARIES AS INDICATED ON
PARSONS PLAN E-111
02/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK UNDERGROUND AS INDICATED ON PARSON PLAN E-11
2. OK 3/0 UFER FROM COLUMN LINE A12 TO A28
02/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 2 - 5" PVC TO XFMR #3
LOCATION OK 12 - 4" PVC TO XFMR #3
2. OK U.G PVC TO MSB-1
02/21/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSONS PLAN E-111
02/20/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3/0 TO BUILDING STEEL COLUMN LINE 2 & 4
BETWEEN P & Q COLUMNS
2. OK 1" PVC U.G TO 10 POLE LIGHTS SOUTH PARKING LOT
3. OK 2 - 5" PVC 13.8 FROM COLUMN LINE 15 TO 8 SOUTHSIDE OF BUILDING
4. OK 4 - 2" PVC FOR BATTERY CHARGING PANELS U.G
02/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 3/0 TO BUILDING STEEL COLUMN LINE 8 & 10
BETWEEN P & Q COLUMNS
02/12/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDERGROUND IN C4 ELECTRIC CLOSET
02/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 3/0 TO BUILDING STEEL COLUMN LINE 2, 4, 6, 8, 10 AND 11
BETWEEN A & B COLUMNS
02/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSONS PLAN E-111
02/07/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/06/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 12 - 4" PVC FROM JUST OUTSIDE FOOTING TO MSB-1
2. OK U.G AS INDICATED ON PARSONS PLAN E-111
02/04/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
01/30/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED BY BRUCE
01/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSONS PLAN E-111
01/28/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
01/25/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED BY BRUCE
01/24/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G IN GIFT WRAP AREA
2. OK 3/0 UFER GROUND COLUMN LINE 1 TO 12 SOUTH FOOTING
01/23/2008 ELECTRIC - UNDERGROUND Partial Approval OK 2 - 5" PVC U.G FOR PRIMARIES UNDER BUILDING SLAB
01/22/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSONS PLAN E-111
01/18/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED BY BRUCE
01/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON PARSON PLAN E-111
01/16/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 12 - 4" PVC FROM MSB-3 TO JUST PAST BUILDING FOOTING
01/15/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UG AS INDICATED ON DRAWING E-111 PARSONS
01/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK UFER GROUND FROM
COLUMN LINE A1 TO A12 3/0 COPPER
2. OK 12 - 4" PVC FROM M5B2 TO JUST PAST BUILDING FOOTING
01/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AS INDICATED ON DRAWING FROM MSB-2
PARSONS PLAN E-111