Permit: T07CM04125

Parcel: 10703141D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/20/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ON 1/23/08 OK TO COVER WALL
NEED TO SEE CLOSET FLANGES
01/18/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEE NOTES #1 & #3 ABOVE
2. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
01/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SEE NOTE #24 ON PLUMBING SPECS P-1 INSULATION
2. SEE NOTE #04 ON PLUMBING SPECS P-1 HANGERS
3. ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
4. ALL WATER PIPING TO BE SUPPORTED IN AN APPROVED MANNER