Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* IN PANEL 1. PANEL DIRECTORY NOT CORRECT 2. SHEETMETAL SCREWS NOT ALLOWED ON GROUND BAR 3. PROPERLY GROUND PANEL, HAVE LUG ON WASHER? 4. PROPERLY IDENTIFY PHASE CONDUCTORS WATER HEATER 1. SECURE MC WITHIN 12" OF TERMINATIONS 2. NEED PROPER LOCKOUT FOR BREAKER (NOT LOCK DOG) OR INSTALL DISCONNECTING MEANS AT WATER HEATER EMERGENCY LIGHTING NOT PER PLAN CHECK ROOF |
|
| 03/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK NOT COMPLETE NEED TO PAY REINSPECTION FEE |
|
| 03/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WORK CALLED BEFORE READY DO NOT CALL BEFORE COMPLETE AND PER PLAN |