Permit: T07CM04121

Parcel: 115011510


Addresses:

340 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04121

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - FINAL Approved PER INSP CARD
11/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROPERLY MOUNT SMOKE DETECTORS
2) PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES
11/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL WHEN METER 336 & 340 ARE ENERGIZED
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOFTOP EQUIPMENT TO BE LABELED BY MEANS SUITABLE FOR THE ENVIRONMENT, NOT SHARPIE
2. IDENTIFY "SERVICE DISCONNECTS" AS SUCH AND INSTALL ADDRESSES ON METER BASES
3. INSTALL SMOKE DETECTORS PER MANUFACTURES INSTRUCTIONS
4. CALL BOTH IN @ SAME TIME
10/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY

1. ALL (NEW) WIRING AND EQUIPMENT TO BE EXPOSED FOR INSPECTION - OPEN WALLS & CEILINGS AS NEEDED

ON ROOFTOP
1. IDENTIFY NEW UNITS, DISCONNECTS AND PANEL DIRECTORY
2. IDENTIFY WHITE USED AS HOT
3. INSTALL PROPERLY SIZED FUSES
4. NEED ROOFTOP SERVICE GFI RECEPTACLE
5. IDENTIFY UNITS DATA PLATES
6. SECURE RACEWAYS TO ROOF
7. DISCONNECT NOT TO HAVE DRAIN PIPE IN FRONT OF IT