Permit: T07CM04118

Parcel: 11011181B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
01/14/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
01/08/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE ACCESS DOORS AT ALL FIRE DAMPERS
FIRE CAULK AROUND ANGLES AS NEEDED
- PROVIDE A DUCT SMOKE DETECTION SYSTEM IN PLENUM CEILING FOR UNIT SHUT DOWN W/AUDIBLE & VISIBLE ALARM
- OK PARTIAL CEILING TILES
01/04/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*