Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - FINAL | Approved | ||
| 01/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO OCCUPY SOUTH HALF SUBJECT TO OTHER INSPECTORS |
|
| 01/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH INSTALL OFFICE FURNITURE AND TIGHTEN ALL FITTINGS 2. EM & EXIT LIGHTING TO BE AS PER 700.12 |
|
| 01/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH CEILING BOX 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. BOXES MORE THAN 1/8" AROUND 314.21 4. TIGHTEN LOOSE FITTING - OFFICE FURNITURE 5. REVISE PANEL DIRECTORIES PER 408.5 6. MODULAR FURNITURE TO BE AS PER 605.7 7. CONDUCTOR COLORS TO BE AS PER CITY AMENDMENTS ENTIRE LENGTH 8. FINISH INSTALL OF OFFICE MODULAR FURNITURE 9. PLEASE VERIFY EM & EXIT LIGHTING PER 700.12 |