Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04118
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
01/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PHASE ONE |
|
01/08/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC CABLE AS PER CODE - USE APPROVED STRAPS AND METHODS 2. TIGHTEN LOOSE FITTINGS 3. BOND BUSHING AT 250V REDUCING WASHERS |
|
01/04/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. SECURELY ATTACH FIXTURES TO GRID - 410.16 2. SUPPORT MC CABLE OVER 6' IN LENGTH AS PER 330.30 ALSO 300.11 3. CONDUCTORS TO BE COLORED PER 210.5 OF CITY AMENDMENTS 4. PREVENT DIE ELECTRIC CONTACT 5. MAINTAIN WORKING CLEARANCES AT DISCONNECTS 6. SUPPORT MEANS NOT TO BE OTHER WIRING METHODS 7. OLD VDV CABLING TO BE AS PER 725.3 NEW 725.6, 800.24, 300.11 |