Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM04118

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - ABOVE CEILING Approved
01/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK PHASE ONE
01/08/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT MC CABLE AS PER CODE - USE APPROVED STRAPS AND METHODS
2. TIGHTEN LOOSE FITTINGS
3. BOND BUSHING AT 250V REDUCING WASHERS
01/04/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SECURELY ATTACH FIXTURES TO GRID - 410.16
2. SUPPORT MC CABLE OVER 6' IN LENGTH
AS PER 330.30 ALSO 300.11
3. CONDUCTORS TO BE COLORED PER 210.5 OF CITY AMENDMENTS
4. PREVENT DIE ELECTRIC CONTACT
5. MAINTAIN WORKING CLEARANCES AT DISCONNECTS
6. SUPPORT MEANS NOT TO BE OTHER WIRING METHODS
7. OLD VDV CABLING TO BE AS PER 725.3
NEW 725.6, 800.24, 300.11