Permit: T07CM04118

Parcel: 11011181B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04118

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - INTERMEDIATE Approved
12/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONDUCTOR TO BE COLORED FOR VOLTAGES PER AMENDMENTS 210.5(C)

OK WALLS ONLY PHASE 1
12/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT M/C CABLES WITHIN 12" -- 330.30
2. PROTECT M/C CABLES INSIDE STUD CHANNELS
3. PROTECT M/C CABLE AS PER 330.17 & 300.4
4. USE APPROVED STRAPS FOR M/C CABLE
5. PLEASE PROVIDE AUTHORIZATION FOR USAGE OF
M/C CABLE