Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04114
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
04/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH ITEM #1, 5, 7 AND 11 FROM PREVIOUS INSPECTION |
|
04/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ONLY ONE CONDUCTOR PER LUG 2. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FOR BOTTOM OF PANEL 3. TIGHTEN LOOSE FITTINGS 4. WHERE IS DISCONNECTING MEANS FOR ICE MACHINE 5. SEAL CONDUITS TO WALK IN PER 300.7 6. PLEASE VERIFY LISTING & LABELING OF EQUIPMENT DIP FREEZER - MISSING EQUIPMENT AS PER PLANS 7. CONDUCTOR COLORS TO BE BLACK, RED, BLUE PER CITY AMENDMENTS 8. PANEL MISSING POUR HARDWARE 9. BOXES MORE THAN 1/4" OR 1/8" AROUND 314.20, 314.21 10. EXIT LIGHTS NOT WORKING 11. MISSING TRACK HEADS |