Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04114
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/08/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE *VDV REMOVED - OK ON FINAL CK CASH WRAP CONDUCTORS ON FINAL |
|
04/07/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |
|
04/04/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* REMOVE TILE TO INSPECT - NO APPROVAL WAS GIVEN TO START TILES |
|
04/03/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABLING AS PER 300.11, 725.24 & 3 2. CANNOT SUPPORT ELECTRIC OFF OF GRID SUPPORT WIRES 300.11 3. SUPPORT CONDUITS 10' INTERVALS 4. FINISH JUNCTION BOXES |